The ultimate guide to proper cable sizing for your drive technology – including a calculator!
Why is the correct motor cross-section so important?
A correctly sized motor cross-section is crucial for the safety and efficiency of your system. It prevents overheating, fire hazards, and unnecessary energy losses, which can account for 5% of the energy in a 10 kW motor. In addition, it ensures the longevity of the motor.
What main factors influence the calculation of the motor cable cross-section??
The key factors are the current consumption of the motor (I), the cable length (L), the permissible voltage drop (ΔU, typically <3%), the conductivity of the cable material (γ) (e.g. copper approx. 56 m/Ω·mm²) and the power factor (cos φ) of the motor.
What formula is used for the cross-section calculation for three-phase motors (400V)?
For three-phase motors, which are commonly used in industry, a common formula is: A = (1.732 * L * I * cos φ) / (γ * ΔU). Here, A stands for the cross-section in mm², L for the length in meters, I for the current in amperes, cos φ for the power factor, γ for the conductivity, and ΔU for the voltage drop in volts.
What happens if the motor cross-section is chosen too small?
A too small motor cross-section leads to a higher electrical resistance. This causes heat development, which can damage the cable insulation and lead to fire hazards. Moreover, it results in an increased voltage drop, which reduces motor performance and can damage the motor.
How does the installation type affect the required cable cross-section for motors??
The installation type (e.g., in pipes, on trays, underground) and ambient temperature influence the current carrying capacity of the cable. A bundling of cables or high ambient temperatures can hinder heat dissipation and therefore often require a larger cross-section, than would be purely computationally necessary for the voltage drop. This is taken into account in standards such as DIN VDE 0298-4.
Are online calculators sufficient for the motor cross-section ?
Online calculators provide a good initial orientation for the required motor cross-section. However, they do not substitute detailed professional planning, which considers all specific operating conditions, standards, and safety aspects. In critical applications, expert review is essential.
What motor cross-section does an 11kW three-phase motor require, for example?
For an 11 kW three-phase motor (~22A at 400V), a minimum cross-section of 4mm² copper is required. Depending on cable length, installation type, and required voltage drop, however, a cross-section of 6mm² is often recommended, to ensure sufficient reserves.
When should I consult a specialist like ATEK Drive Solutions for the sizing of the motor cross-section? Professional advice is essential in case of
Professionelle Beratung ist unerlässlich bei complex systems, high motor power, critical applications (e.g. explosive areas), drives with frequency converters (EMC aspects), or if uncertainties regarding standards and sizing exist. ATEK Drive Solutions supports you with expertise in the design of complete drive trains..
The correct choice in the motor cross-section is crucial for safety and efficiency; an undersized cross-section can lead to overheating, fire hazards and energy losses of over 5% .
The calculation of the motor cross-section? takes into account current, length, voltage drop (target <3%), material, and power factor. Always choose the next larger standard cross-section and check the current carrying capacity according to DIN VDE standards..
Online calculators provide guidance, but for complex systems or high powers, professional advice is essential, to ensure compliance with standards and reduce the risk of failures due to overheating or voltage drop by over 80%..Learn how to determine the optimal motor cross-section to avoid overheating, voltage losses, and costly failures. With practical tips and an easy calculator!
The correct sizing of the motor cross-section is crucial for the performance and safety of your drive technology. But how do you calculate it correctly? We will show you! Do you need personalized advice? Contact now contact our experts.
Do you need support in sizing the optimal motor cross-section for your application?
Request free expert advice now!
Introduction to cable cross-section in motors: The right motor cross-section
The correct choice in the motor cross-section is fundamental for plant safety and efficiency. This guide helps determine the optimal cable cross-section for motors and prevent misinvestments.
Understanding the basis for safe motor operation
Incorrectly sized cables, especially an insufficient motor cable cross-section, cause production downtimes. Missing correct cable cross-section poses risks: overheating, fire hazards, performance losses in motors.. A 10 kW motor with too small a cable cross-section may suffer from 5% energy loss.
Recognizing the consequences of incorrect sizing
A too low motor cross-section increases the electrical resistance. Consequences: heat development (damage to cable insulation, fire hazard), significant voltage drop. More than 4% voltage drop reduces the power of a three-phase motor and shortens its lifespan, highlighting the importance of the correct cross-section calculation for motors.
Important influencing factors at a glance
The choice of the right motor cross-section? depends on current consumption, ambient temperature, and installation type. Cable length is critical: longer cables require larger cross-sections for the motor due to higher voltage drop. Doubling the length may require the next larger standard cross-section for the motor (e.g., for 3% voltage drop).Calculation of the motor cross-section?: Formulas and influencing factors
Fundamental formulas for the calculation
The cable cross-section (A), i.e. the relevant conductor cross-section for the motor, varies depending on the type of current. For three-phase current (400V), e.g., for servo motors,the formula for calculating the required motor cross-section?is: A = (1.732 * L * I * cos φ) / (γ * ΔU). (L=length, I=current, cos φ=power factor, γ=conductivity, ΔU=voltage drop in volts). Correct variables are crucial for the exact determination of the cable cross-section for motors. Copper (γ) has a conductivity of approx. 56 m/(Ω·mm²).
- The basic formula for three-phase is: A = (1.732 * L * I * cos φ) / (γ * ΔU).
- The correct entry of all variables (length, current, power factor, conductivity, voltage drop) is crucial for an accurate result in determining the motor cross-section?.
- motor current (I) and cable length (L) are the primary factors that determine the required motor cross-section cross-section.
- The power factor (cos φ, typically around 0.85) influences the apparent power and thus the current consumption.
- A permissible voltage drop (ΔU), often limited to 3%, must be considered in the calculation of the cable cross-section for motors.
- The conductivity of the material (e.g., copper γ ≈ 56 m/(Ω·mm²)) is an important parameter in the formula.
- In the practical example of the motor cross-section calculation, the next higher standard cross-section is always chosen to ensure safety and efficiency.
The key influencing factors in detail
Motor current (I) and cable length (L) are primarily responsible for the required motor cross-sectioncross-section. A 30A motor needs a larger cable cross-section than a 10A motor. At 50m, a cross-section of 6 mm² instead of 4 mm² may be needed for the motor (max. 3% voltage drop). Power factor (cos φ ~0.85) and ΔU (typ. 3%) are other important parameters for sizing the motor cross-section.
Practical example: Cross-section calculation for a three-phase motor
A 15kW three-phase motor (400V, cosφ 0.87, ~27A) requires a specific cross-section at 45m cable length. motor cross-sectionTarget: ≤2% ΔU (8V). The calculation of the motor cross-section yields: A=(1.732*45m*27A*0,87)/(56*8V)≈4,08mm². Next higher standard cross-section (6mm²) for safety, efficiency, and optimal motor performance..Practical aspects of cable selection for the motor cross-section and standards.
Current carrying capacity: More than just a number.
The calculated motor cross-section alone is not enough. The current carrying capacity (maximum current without overheating) is also crucial for selecting the right cable cross-section for motors. It depends on installation type (pipe, tray, underground) and ambient temperature. A cable free in air (25°C) can carry 20% more current than in an insulated duct (40°C), which influences the requirements for the motor cross-section cross-section.
Observe relevant standards and regulations.
The selection of cables for the motor cross-section is subject to standards (safety, interoperability). DIN VDE standards (e.g. DIN VDE 0298-4) are relevant here. They define current carrying capacities, correction factors (concentration, temperature); important for planning the correct motor cross-section. DIN EN 60228 (VDE 0295) specifies the conductors.
Tools: wisely use tables and online calculators
Tables and online calculators provide a first orientation for the motor cross-section. These tools simplify the selection but do not replace detailed planning (considering specific factors and standards) for the optimal motor cross-section. A calculator may suggest 4mm² as the motor cable cross-section, but the standard may require 6mm².Typical use cases and examples for the motor cross-section
cross-section recommendations for common motor powers
For 400V three-phase motors, there are guidelines for the motor cross-section:
- 7.5kW (~15A): at least 2.5mm² as the conductor cross-section for the motor (for long cables or unfavorable conditions: 4mm²).
- 11kW (~22A): The lower limit for the motor cross-section is 4mm², recommended 6mm².
- 22kW (~40A): at least 6mm² as the cable cross-section for the motor (often 10-16mm²).
These guidelines for the motor cross-section must always be validated by accurate calculation and checking of current carrying capacity according to DIN VDE 0298-4.
Practical example 1: Drive for a conveyor belt
Conveyor belt (5.5kW motor, 400V, 11A), 30m cable. The calculation for the motor cross-section results in about 1.5mm². Due to cable channel installation (concentration) and for robustness, a motor cable cross-section of 2.5mm² copper was chosen. This provides safety and minimizes losses.
Practical example 2: Servo motor in a packaging machine
Ein Servo motor (18A peak current, 8m line) requires a specific motor cross-section. The cross-section must be designed for the peak current and a low voltage drop. A conductor cross-section of 2.5mm² is sufficient here, also considering system dynamics (a high voltage drop disturbs the controller). An accurate design of the motor cross-section is particularly important here.Avoiding errors and safety instructions when choosing the motor cross-section?
Recognize and avoid common mistakes in cable selection
An underestimated voltage drop (especially with long lines) leads to power loss and motor overheating, when the motor cross-section is too small. Neglecting installation conditions and ambient temperatures, which reduce the current carrying capacity, is critical when determining the motor cable cross-section. With 3 cables in a pipe, the permissible current can drop by up to 30%, requiring a larger motor cross-section .
- Never underestimate the voltage drop, especially with long cable runs, to avoid power losses and overheating; this is a key factor for the correct motor cross-section.
- Always consider the installation conditions and ambient temperatures, as they can significantly affect the current carrying capacity of the cables and thus the requirements for the motor cross-section .
- Remember that the concentration of cables, for example in an installation pipe, can reduce the permissible current by up to 30% or more, which must be considered when choosing the conductor cross-section for the motor.
- Have electrical installations, including the selection of the motor cross-section?, carried out exclusively by qualified professionals, observing all relevant safety regulations.
- Use only standard-compliant and approved cable material suitable for the application with the appropriate motor cross-section, to minimize risks.
- Ensure proper installation and firm, correct connections to avoid transition resistances and potential fire hazards; thermography can help proactively identify issues related to the motor cross-section .
- Do not hesitate to seek professional advice, especially for complex systems, high motor powers, critical applications (e.g. Ex areas), or uncertainties about standards, EMC and the correct motor cross-section sizing.
Safety first: Important installation instructions
Electrical installations are specialized work and require adherence to safety regulations, even when determining the motor cross-section?. Use only standard-compliant and approved cable material for the application. Proper installation of the cable with the correct motor cross-section prevents damage. Firm connections minimize transition resistances. Loose connections (fire hazard) can be proactively detected by thermography.
When is professional advice necessary?
Online tools provide only a guide for the motor cross-section. Professional advice is essential for complex systems, high motor powers, critical applications or uncertainties regarding standards. For example, in Ex areas or frequency inverter drives (EMC), an exact determination of the motor cross-section is crucial. Technical support ensures the optimal design of the cable cross-section for motors.
The correct determination of the motor cross-section? is essential for the safety, efficiency, and longevity of the system. Taking into account formulas, influencing factors, standards, and current carrying capacities prevents errors and ensures reliable planning of the required conductor cross-section for the motor.