What a frequency converter does to the motor and what you need to consider regarding connection, field weakening, cooling, insulation, bearing currents and EMC in converter operation.

AI This article was created with the help of AI.

What changes for a motor with a frequency converter

Connected directly to the mains, an asynchronous motor runs at a fixed speed that depends on the number of pole pairs and the mains frequency. Connected to the frequency converter (variable frequency drive, VFD), it instead receives a voltage of variable magnitude and frequency[1]. In addition to asynchronous motors, it also operates permanent-magnet synchronous motors; servo converters with inputs for the rotor position serve as positioning drives[1]. How the converter is built from a rectifier, DC link and inverter and how it works is explained in our article Frequency converter: function, design and selection at a glance.

This allows the speed to be adjusted steplessly from almost zero to the rated speed without the torque dropping; how far this applies in continuous operation depends on the cooling. Via a frequency ramp, the motor starts without strong overcurrent peaks, and with a descending ramp it decelerates[1]. In addition, the converter often takes over protective functions against overcurrent, overload and overtemperature and can reverse the direction of rotation[2]. If you only need to limit the start, a soft start may be sufficient; our article Soft starter vs. frequency converter weighs up the options.

Control methods and speed range

In simple V/f mode, the converter keeps voltage and frequency proportional up to the rated frequency. This results in constant torque over wide ranges; at very low speeds, a voltage boost compensates for the winding resistance. Since the speed fluctuates with the load, V/f is only sufficient where requirements for speed constancy are low and there is no heavy starting. Field-oriented control (vector control), on the other hand, controls reactive and active current separately on the basis of a motor model; below the rated speed, the torque can briefly amount to a multiple of the rated torque[1].

Above the rated frequency, the output voltage reaches its maximum value and the motor operates in field weakening[1]. There, the mechanical power remains constant, the rated torque decreases with increasing frequency, and the breakdown torque decreases with the square of the frequency[3]. More on calculating speed in the article Speed of electric motors.

Range (50 Hz mains)VoltageTorquePower
Base speed range up to 50 Hzproportional to frequency (V/f = constant)constant, reduced with self-ventilation and low speedincreases with speed
Field weakening above 50 Hzconstant (maximum value)decreases with increasing frequencyconstant
87 Hz operation (230/400 V motor in delta on a 400 V converter)proportional up to 87 Hzrated torque up to 87 Hz, to be checked thermally because of increasing iron lossestheoretically up to a factor of 1.7, at most about 1.45 when utilised according to thermal class B[3]

Star or delta on 230 V and 400 V converters

A motor with the nameplate rating 230/400 V has windings for 230 V. In star connection, each winding receives the line voltage divided by √3. On a converter with 3 × 400 V output voltage, the motor is connected in star; on a converter with 3 × 230 V, as supplied by many single-phase-fed 230 V devices, it is connected in delta. With the wrong connection, the winding receives either only around 58% of its voltage, which reduces the torque to about one third, as with star starting[2], or √3 times the voltage, which overexcites and overloads the motor. Our article Star or delta explains the basics of both connections.

Special case of 87 Hz operation: a 230/400 V motor in delta on a 400 V converter can be operated up to 87 Hz with rated torque and thus at higher speed if the V/f characteristic is set so that the converter only outputs 400 V at 87 Hz (i.e. 230 V at 50 Hz). The converter must then supply the delta current, i.e. be designed for the rated current of the motor at 230 V. This increases the load from the shaft-mounted fan and the frequency-dependent iron losses, and the motor can be thermally or mechanically overloaded[1]. The value of 87 Hz results from the factor 1.73, i.e. √3 · 50 Hz[3].

Thermal design of the motor

A self-ventilated motor (IC411) cools less effectively at low speed because its fan runs more slowly. In continuous operation, the permissible torque must then be reduced, the more so the larger the speed range and the lower the minimum frequency. A force-ventilated motor (IC416) with a mains-fed fan provides full torque even below 50 Hz. For short-time operation of a few minutes, full torque is also available with self-ventilation; however, an increased breakaway torque requires a higher current from the converter[3].

Because of the additional losses caused by harmonics, manufacturers usually prescribe power derating; one technical article cites 5 to 10% of the rated power, provided the motor does not have sufficient thermal reserve[4].

With a gear motor on a frequency converter, the gear ratio helps: if it is selected so that the motor runs close to the rated frequency at the most frequent operating point, the range with reduced cooling remains small[3]. Motors with a mounted frequency converter also reduce the wiring and interference suppression effort[2].

Winding insulation, bearings and EMC

Converters switch with steep edges; with 400 V mains operation, the DC link voltage is 560 V. On long motor cables, for example over 25 m, reflections can generate voltage peaks of up to twice the DC link voltage and place lasting stress on the winding insulation[1]. Motors of more recent production with thermal class F insulation can usually be used at the 400 V level without concern; you should nevertheless obtain a confirmation of suitability from the manufacturer. For older motors, the critical cable length must be calculated and a filter provided if it is exceeded[4].

Via capacitances in the motor, currents can flow from the shaft through the bearings to the housing and cause electrical erosion there[1]. An insulated bearing, usually on the non-drive end, provides a remedy. If the drive-end bearing were insulated, the voltage would be applied to the bearings of the driven machine or the gearbox if the coupling is not insulated; an insulated coupling or a grounding brush parallel to the non-insulated bearing complements the protection[4].

For EMC, the motor cable often has to be shielded, with the shield connected over a large area at both ends. Sine-wave filters allow long supply cables and relieve the motor. Limits for interference emissions are set by the product standard EN 61800-3, and for mains harmonics by the EN 61000-3 series; line reactors mitigate them. The switching frequency is usually between 2 and 20 kHz: higher frequencies approximate the sine wave better and reduce motor losses, but increase the switching losses in the converter[1].

Planning in the drive train

Checklist for project planning:

  • Nameplate: winding voltage and rated frequency determine the connection, and the rated current in this connection determines the converter size.
  • Speed range and load characteristic: they decide between self-ventilation and forced ventilation and on power reserves[3].
  • Braking operation: excess energy is converted into heat via a brake chopper and braking resistor or fed back into the grid via a regenerative converter[1].
  • Commissioning: parameterise the motor data; many converters measure the drive characteristics themselves[1]. Before working on the device, wait for the DC link discharge time specified in the operating instructions.

As a supplier for the complete drive train, we at ATEK Drive Solutions design motor, gearbox and brake to fit precisely from a single source, including for operation on a frequency converter. You will find an overview of our IEC standard motors in our product range, and we will be happy to advise you personally on your specific application via our contact page.

Frequently asked questions

Can any motor be operated with a frequency converter?

Many standard asynchronous motors are suitable. Check insulation, thermal reserve and bearings. Single-phase capacitor motors can also be speed-adjusted with suitable converters, but without a higher starting torque.

What are the advantages of a motor with a frequency converter?

Infinitely variable speed, ramps for acceleration and deceleration, reversal of the direction of rotation and integrated protective functions; with pumps and fans, additional energy savings (see below).

What matters when matching converter and motor?

Motor power and motor current, mains voltage (230 V single-phase or 400 V three-phase), load characteristic and breakaway torque, braking operation and ambient conditions.

How is a 230/400 V motor connected to a frequency converter?

In star on a converter with 3 × 400 V output voltage, in delta on a converter with 3 × 230 V. An exception is intentional 87 Hz operation in delta on a 400 V converter, with the V/f corner point shifted to 87 Hz and a converter that supplies the delta current.

What EMC measures does a motor with a frequency converter need?

A shielded motor cable with the shield connected over a large area at both ends, filters as required and line reactors against mains harmonics.

What role does the PWM frequency play?

It is a compromise: higher switching frequencies reproduce the sine wave better, and from about 16 kHz the switching noise disappears from the clearly audible range. In return, the switching losses in the converter increase, and the more frequent switching edges can worsen EMC and insulation stress.

How much energy does a motor with a frequency converter save?

With pumps and fans, the drive power decreases roughly with the cube of the speed: at half the flow rate, the drive theoretically needs only one eighth of the rated power, and at 80% speed around half. Converter losses must be added.

Can a frequency converter be integrated into the machine control system?

Yes. Frequency converters usually have digital and analogue inputs and outputs and interfaces for fieldbuses or Industrial Ethernet. Standardised drive profiles are defined in the IEC 61800-7 standard.

Sources

  1. Wikipedia (DE): Frequenzumrichter (frequency converter)
  2. Wikipedia (DE): Drehstrom-Asynchronmaschine (three-phase asynchronous machine)
  3. elektropraktiker.de (DE): Project planning of frequency converter drives
  4. elektropraktiker.de (DE): Stress and selection of converter-fed three-phase asynchronous motors