Fans on electric motors: self-cooling IC411 or forced-ventilation fan IC416, when forced ventilation is needed on a converter and how to retrofit safely.

AI This article was created with the help of AI.

Fans on electric motors: self-cooling and forced ventilation

Whether shaft-mounted fan or forced-ventilation fan: the fan on the electric motor dissipates the heat losses generated in the winding, laminated core and bearings. In enclosed three-phase motors, the housing often has external cooling fins over which the rotor’s fan blows air[1]. This fan impeller with its fan blades sits on the rear shaft end under the fan cowl, which covers the impeller and directs the air flow over the fins. Because the fan impeller rotates with the shaft, the volume of cooling air depends directly on the motor speed.

The type of cooling is described by the IC code according to DIN EN 60034-6 (VDE 0530-6), which classifies the cooling methods of rotating electrical machines[2]. It consists of the letters IC and characteristic codes for the arrangement of the cooling circuit, the coolant and the way the coolant is moved[3]. Two codes are decisive for drive design: IC411 designates self-ventilation with speed-dependent air flow, IC416 forced ventilation with speed-independent air flow[4].

CharacteristicIC411 (self-cooling)IC416 (forced ventilation)
Fan driveFan impeller on the motor shaftown fan motor with separate mains connection
Air volumedrops with speedconstant, independent of motor speed
Continuous torque at low speedmust be reducedfully available
Noise above 50 Hzrises significantly with speedusually lower
Typical useMains operation at fixed speedConverter operation with a large control range

At what speed self-cooling is no longer sufficient

On a frequency converter, the speed is decoupled from the supply frequency, and this is precisely where self-cooling reaches its limit. With self-ventilation (IC411), the thermally permissible torque must be reduced at low speeds; with forced ventilation (IC416), it is fully available even at frequencies below 50 Hz. The larger the control range and the lower the minimum frequency, the more the torque must be reduced in continuous duty S1. The reduction is only necessary if the motor runs continuously or for long periods at low speed; for short-time duty of a few minutes, the full torque is available[4]. If a controlled motor runs down to near standstill, cooling by the rotor fan is largely absent[1].

There is therefore no universally valid frequency limit. The load characteristic and the derating curve in the motor data sheet are decisive. With pumps and fans, the power consumption drops with the cube of the speed, which reduces the risk of overheating. With mixers, on the other hand, the torque can increase as the speed drops, so that the integrated fan may no longer be sufficient; with a constant load, the motor torque must be limited for reduced speeds as early as the design stage. According to the same guide, larger converter motors should have a fan with constant speed[5].

  • Constant load torque over a large speed range, for example with conveyors or mixers.
  • Long operating phases far below the rated speed, or holding at standstill.
  • Attachments on the rear shaft end, such as an encoder, that take up the space of the shaft-mounted fan.
  • Noise limits during operation above 50 Hz, because fan noise depends heavily on speed[4].

If any of these points applies, consider a forced-ventilation fan. How to protect motors thermally for continuous operation is described in our article Thermally protected motors in continuous operation.

Retrofitting a forced-ventilation fan: mounting and connection

The question of forced ventilation often only arises when an existing mains motor is subsequently connected to a frequency converter. Forced cooling may then be necessary at lower speeds; older motors that were not built for converter operation can also suffer insulation damage from the switching edges of the voltage[6]. Before retrofitting, you should therefore check whether the motor is suitable for converter operation.

  • Mechanics: remove the fan cowl and shaft-mounted fan, and mount the forced-ventilation unit in place of the cowl. The dimension sheets of the motor and unit show whether the shaft end needs to be modified.
  • Air path: leave space in front of the air inlet; some motors require a clearance of at least a quarter of the shaft height[5].
  • Supply: operate the forced-ventilation fan directly on the mains so that it works independently of the converter with constant speed and cooling effect[4].
  • Direction of rotation: with three-phase forced-ventilation fans, check the direction of rotation after connection.
  • Protection: protect the fan with its own protective device, independently of the main motor.

The reason for the mains supply: the speed of the forced-ventilation fan depends on the so-called external supply at 50 or 60 Hz[7]. At the converter output, it would slow down with the main motor and lose its effect precisely where it is needed.

Interlocking and winding protection

A forced-ventilation fan only protects as long as it is running. The control system must therefore ensure that the main motor is only enabled when the forced-ventilation fan is running. If the fan’s protective device trips, the main motor is switched off or locked out. Interlocking via auxiliary contacts of the fan protection and motor contactor is common.

Current-based protection alone is not sufficient for this. Motor protection distinguishes between monitoring the current consumption and directly monitoring the temperature in the windings; the two are often combined. With full motor protection, several PTC thermistors, usually three, are generally installed in series at the points of the winding that are poorly cooled or not cooled at all. An external evaluation unit switches off the contactor via an auxiliary contact in the event of overtemperature[8]. If the fan fails or the air path is contaminated, the winding temperature rises without the current changing. This is precisely the case the PTC thermistors detect.

Degree of protection, hazardous areas and temperature

The forced-ventilation unit must withstand the same ambient conditions as the motor. For the degree of protection according to EN 60529, a first digit of 6 means dust-tight and a second digit of 6 means protection against powerful water jets; IP55 stands for protection against dust in harmful quantities and against water jets[9]. A unit with a lower degree of protection than the motor becomes the weakest link.

In potentially explosive atmospheres, Directive 2014/34/EU for equipment and protective systems applies. Category 3 equipment is intended for Zone 2 (gas) and Zone 22 (dust), category 2 equipment for Zones 1 and 21[10]. A forced-ventilation fan on an explosion-proof motor must therefore, like the motor, correspond at least to the equipment category prescribed for the zone. The ignition sources to be avoided there include hot surfaces, mechanically generated impact or friction sparks and static electricity[11]. For the fan impeller, this means: material and design must be chosen so that it neither produces sparks nor becomes dangerously electrostatically charged, which must be checked particularly for plastic fan impellers.

Temperature also determines service life. Insulation class B is designed for 130 °C, class F for 155 °C; classes F and H are common in industrial motors[12]. Every increase in operating temperature of 10 °C halves the service life[5]. Cooling that is effective even at low speed therefore pays off directly in the service life of the winding.

Sizing the forced-ventilation fan in the drive train

A forced-ventilation fan is not automatically the most cost-effective solution. For small frame sizes up to about 132, no cost advantage is generally to be expected from a forced-ventilation fan. You can also save on motor costs if the required control range is not planned unnecessarily large[4]. Alternatives include a larger motor with reserve at low speed or an adapted gearbox that keeps the motor in a more favourable speed range. In addition, the forced-ventilation fan runs continuously and consumes energy regardless of the operating point of the main motor.

The best solution results from the interaction of motor, gearbox, brake and converter. As a supplier for the complete drive train, we at ATEK Drive Solutions design the motor, gearbox and brake to fit precisely from a single source. You can find an overview of our IEC standard motors in our product range; we will be happy to clarify with you whether your drive needs a forced-ventilation fan via our contact page.

Frequently asked questions

At what frequency does an electric motor need a forced-ventilation fan?

There is no fixed limit. The decisive factors are the load torque at low speed, the control range and the duration. If a self-ventilated motor runs for a long time with constant torque well below 50 Hz, the continuous torque must be reduced; with a forced-ventilation fan, it remains fully available. The permissible values are shown by the derating curve in the data sheet.

What do IC411 and IC416 mean?

Both codes come from DIN EN 60034-6. IC411 is self-ventilation: a fan impeller on the shaft blows air over the cooling fins, and the air volume drops with speed. IC416 is forced ventilation: a separately supplied fan delivers a constant air volume.

Can a forced-ventilation fan be retrofitted to an existing motor?

Yes, as a rule. The fan cowl and shaft-mounted fan are removed, and the unit is mounted in their place. Check beforehand, using the dimension sheets, whether the shaft end fits and whether the motor is suitable for converter operation.

May the forced-ventilation fan run via the frequency converter?

No, it must be connected directly to the mains. Only then does it work independently of the converter with constant speed and cooling effect. At the converter output, it would cool just as poorly at low speed as the shaft-mounted fan.

What thermal protection does a motor with a forced-ventilation fan need?

PTC thermistors in the winding with an evaluation unit are recommended, supplemented by interlocking with the forced-ventilation fan. Current-dependent protection alone does not detect failed or contaminated cooling.

Does a pump or fan drive on a converter need a forced-ventilation fan?

Usually not. With pumps and fans, the power consumption drops with the cube of the speed at lower speeds, so the motor is also relieved thermally at low speed. The situation is different for drives with constant or increasing torque.

What should I look out for when replacing a fan impeller or fan cowl?

The spare part must match the frame size: bore and fastening to the shaft diameter, outer diameter to the fan cowl, material to the ambient conditions; in hazardous areas, the fan impeller must neither produce sparks nor become electrostatically charged, which must be checked especially for plastic. Never operate the motor without a fan impeller or fan cowl, because cooling and protection against contact are then missing.

What voltage is a forced-ventilation fan operated with?

Forced-ventilation fans are available for three-phase and single-phase AC. Choose the voltage to match the available supply; the fan is connected via its own terminal box, separately from the main motor.

Sources

  1. Wikipedia (DE): Drehstrom-Asynchronmaschine (three-phase asynchronous machine)
  2. DKE (DE): DIN EN 60034-6 (VDE 0530-6) Classification of cooling methods (IC code)
  3. BSI: BS EN 60034-6 Rotating electrical machines – Methods of cooling (IC Code)
  4. elektropraktiker.de (DE): Planning frequency converter drives (H. Greiner)
  5. IEA 4E Electric Motor Systems (DE): Energy efficiency guide for electric motors (BMVIT, 2014)
  6. Topmotors (SwissEnergy, DE): Fact sheet no. 25 Frequency converters, 2021
  7. Wikipedia (DE): Frequenzumrichter (frequency converter)
  8. Wikipedia (DE): Motorschutz (motor protection)
  9. Wikipedia (DE): Schutzart (degree of protection)
  10. Wikipedia (DE): ATEX
  11. Wikipedia (DE): Explosionsschutz (explosion protection)
  12. Wikipedia (DE): Isolierstoffklasse (insulation class)