Pole-changing motors explained: Dahlander or separate windings, speed steps, connection, motor protection and the comparison with the frequency converter.

AI This article was created with the help of AI.

What is a pole-changing motor?

A pole-changing motor is a three-phase asynchronous motor built for stepped speed control. A distinction is made between two designs: the Dahlander motor and the motor with separate windings[1]. In both cases, coil groups of the stator winding are switched over in such a way that a different number of pole pairs and thus a different rotating field speed results. The method can only be used with squirrel-cage motors, because with slip-ring motors the rotor winding would also have to be switched over. Alongside changing the slip and the supply frequency, pole changing is one of the three fundamental ways of changing the speed of an asynchronous motor[2].

You can recognize a pole-changing motor by two features: the nameplate and circuit diagram state two or more speeds, and on the terminal board the number comes before the letter (1U, 1V, 1W, 2U, 2V, 2W). With single-speed three-phase motors, it is the other way round[1]. In practice, the terms pole-switching motor, pole-changing three-phase motor or two-speed motor are also common.

Because the method is simple, it is often used when two speed steps are sufficient, for example with pumps and fans[2]. Other typical applications are lathes with two basic speeds[1], crushers, milling applications and hoists, in which one speed is used for transport and the second for positioning the load[3].

Speed steps: number of poles, synchronous speed and rated speed

Which speeds a pole-changing motor delivers is determined by the winding. The synchronous speed of the rotating field is calculated as ns = 60 · f / p, with the supply frequency f in Hz and the number of pole pairs p[1]. The notation with the number of poles is equivalent: ns = 120 · f / number of poles. A 4-pole motor therefore has p = 2 and rotates its field at 1,500 rpm at 50 Hz. How to calculate motor speeds in general is shown in our article Calculating the speed of electric motors.

Under load, depending on design and load, the mechanical speed is lower by the slip, usually 1 to 8 %[1]. For gearbox sizing, it is therefore the rated speed of each step on the nameplate that counts, not the synchronous speed.

Number of polesNumber of pole pairs pSynchronous speed at 50 HzSynchronous speed at 60 HzSpeed at 1 to 8 % slip (50 Hz)
213,000 rpm3,600 rpmapprox. 2,760 to 2,970 rpm
421,500 rpm1,800 rpmapprox. 1,380 to 1,485 rpm
631,000 rpm1,200 rpmapprox. 920 to 990 rpm
84750 rpm900 rpmapprox. 690 to 743 rpm

The speed steps are made up of these numbers of poles. Typical combinations at 50 Hz:

Numbers of polesDesignSynchronous speedsRatio
4/2Dahlander1,500 / 3,000 rpm1:2
8/4Dahlander750 / 1,500 rpm1:2
6/4separate windings1,000 / 1,500 rpm2:3
8/6separate windings750 / 1,000 rpm3:4
6/2separate windings1,000 / 3,000 rpm1:3
8/6/4Dahlander 8/4 plus separate 6-pole winding750 / 1,000 / 1,500 rpm3 steps

Dahlander connection: two speeds in a ratio of 1:2

The Dahlander connection goes back to the Swedish engineer Robert Dahlander, who invented it in 1897[3]. It allows the number of poles to be changed in a fixed ratio of 1:2 and thus the speed in a ratio of 2:1. The windings are tapped: each phase has a start, an end and a centre tap. Because one start and one end each are connected to form a delta at the factory, the Dahlander motor has only six connections on the terminal board[1].

For the low speed, the winding operates in delta. For the high speed, it is connected in double star (YY). In this process, the current direction in half of the coils is reversed, so that the number of effective poles is halved[3]. The power circuit corresponds to the star-delta starting circuit: for the low speed, only the delta contactor switches; for the high speed, the line contactor together with the star contactor. The delta contactor must never switch on together with the line or star contactor; mutual interlocking in the control circuit ensures this[1].

Speed stepConnectionMains connectionOther terminalsContactors
lowDelta (Δ)L1, L2, L3 to 1U, 1V, 1W2U, 2V, 2W openDelta contactor
highDouble star (YY)L1, L2, L3 to 2U, 2V, 2W1U, 1V, 1W bridged (star point)Line contactor and star contactor

The connection diagram of the respective motor is always decisive. As with all three-phase motors, the direction of rotation is reversed via a reversing contactor circuit, which is combined with the pole changing[1].

Depending on the winding design, there are two variants: delta/double star (Δ/YY) for drives with constant torque such as hoists, and star/double star (Y/YY) for drives with quadratically increasing load torque such as pumps[3].

Separate windings: free speed ratios and up to four steps

A motor with separate windings carries at least six windings in the stator core, of which the first three are not connected to the second three. The first winding is designed for the low speed, the second for the high speed; both act on a common squirrel-cage rotor. A specific speed ratio is not fixed; 3:4, 2:3, 1:2, 1:3 and 1:4 are typical. The ratio 1:2, however, is usually implemented with the Dahlander connection[1].

The windings are usually connected internally in star or delta. The required contactor circuit is similar to a reversing contactor circuit, only without swapping two line conductors. For three speeds, a Dahlander winding and a separate winding are combined; for four speeds, two separate Dahlander windings. The terminal boards are then 9- or 12-pole[1]. Because several windings share the slot space, you should check the power and rated current of each step on the nameplate when selecting a motor and not go by the frame size of a single-speed motor.

CharacteristicDahlander windingSeparate windings
Windingsone tapped windingtwo electrically separate windings
Speed ratiofixed 1:2freely selectable, e.g. 2:3, 3:4, 1:3
Terminals66 (windings connected internally), 9 or 12 for more steps
Connectionlike star-delta connection, Δ or Y versus YYlike reversing contactor circuit without phase swap
More than two steps4 steps with two Dahlander windings3 steps in combination with a Dahlander winding

Sizing: load torque, switchover and motor protection

Sizing starts with the load characteristic of the driven machine. For centrifugal pumps, the affinity laws apply: the flow rate changes proportionally to the speed, the head with the square and the power consumption with the cube[4]. A pump running at half speed in the low Dahlander step delivers half the flow and needs only around one eighth of the power. The Y/YY variant is suitable for such loads. Conveyor belts and hoists, on the other hand, require an approximately constant torque; here, the power drops only linearly with the speed, and the Δ/YY variant is the usual choice[3].

Switching from the high to the low step deserves special attention. At this moment, the rotor turns faster than the new, slower rotating field. The machine runs supersynchronously, i.e. it works as a generator with negative slip, brakes the shaft and feeds active power back into the grid[2]. What happens physically is explained in our article on slip in the asynchronous motor. The large speed jumps stress the mechanics and lead to faster wear[3]. For fans with a large flywheel mass or for gearboxes with high ratios, a switchover delay that lets the drive run down first is therefore advisable.

For motor protection, the following applies: each speed step has its own rated current, so the overload protection must match the step that is currently active. PTC thermistors in the winding provide additional protection. Their resistance rises abruptly at the rated response temperature; they are standardized in DIN 44081 and DIN 44082 and, because they measure the winding temperature directly, are suitable for all motor types regardless of current type and connection[5]. This is particularly useful with pole-changing motors: with self-ventilated motors, the fan sits on the motor shaft and delivers correspondingly less cooling air in the low step.

Pole-changing motor or frequency converter?

Speed control via a frequency converter is state of the art today. The converter changes frequency and voltage together and can thus control the asynchronous motor over a very wide speed range[2]. What needs to be considered for the motor and converter is described in our article Motor with frequency converter. The pole-changing motor, by contrast, manages without power electronics. Since there is no pulse switching, there are no converter losses, and the design is simpler. On the other hand, there is the wear caused by the speed jumps and harmonics during switchover[3].

When it comes to energy efficiency, it is worth taking a closer look. Since 1 July 2021, single-speed three-phase motors with 2, 4, 6 or 8 poles from 0.75 to 1,000 kW must in principle achieve at least efficiency class IE3. Motors with multiple speeds, i.e. with several windings or a switchable winding, are exempt from these efficiency requirements[6]. There is therefore no mandatory minimum class for them; compare the efficiencies of both steps using the manufacturer’s data with a solution consisting of an IE3 motor and a converter, based on your load profile.

  • Are two to four fixed operating points sufficient? Then a pole-changing motor is a simple, robust solution.
  • Should the speed follow the process steplessly, or are smooth ramps required? Then there is no way around the frequency converter.
  • Does the system run predominantly in one step? Then the efficiency at this operating point determines the energy costs.
  • Are frequent switchovers under a large flywheel mass to be expected? Then design the mechanics, gearbox and switchover delay together.

The number of poles, gear ratio and brake together determine which output speeds the machine actually reaches. As a supplier for the complete drive train, we at ATEK Drive Solutions design the motor, gearbox and brake to fit precisely from a single source, whether with fixed speed steps or for operation on a frequency converter. You can find an overview of our IEC standard motors in our product range, and we will be happy to advise you personally on your specific application via our contact page.

Frequently asked questions

What is the difference between a Dahlander winding and separate windings?

The Dahlander winding is a single tapped winding that delivers two speeds in a fixed ratio of 1:2 by switching from delta or star to double star. Separate windings are two electrically independent windings, one for each speed. This also makes ratios such as 2:3, 3:4 or 1:3 possible.

How do I recognize a pole-changing motor by its nameplate?

The nameplate and circuit diagram state two or more speeds or numbers of poles, usually with their own power and current for each step. On the terminal board, the number comes before the letter, i.e. 1U, 1V, 1W and 2U, 2V, 2W.

What speeds does a two-speed pole-changing motor have?

That depends on the numbers of poles. At 50 Hz, a 4/2-pole Dahlander motor delivers synchronous speeds of 1,500 and 3,000 rpm, an 8/4-pole motor 750 and 1,500 rpm. A 6/4-pole motor with separate windings runs at synchronous speeds of 1,000 and 1,500 rpm. The rated speeds are lower by the slip.

Can a pole-changing motor have three or four speeds?

Yes. Three speeds result from one Dahlander winding plus one separate winding, four speeds from two separate Dahlander windings. The terminal boards are then 9- or 12-pole.

What is a double star connection?

In the double star connection (YY), the two halves of each winding phase are connected in parallel and the terminals 1U, 1V, 1W are connected to form a star point, while the mains is connected to 2U, 2V, 2W. In the Dahlander motor, this gives the high speed.

Why does the Dahlander connection need interlocking?

If the delta contactor and star contactor closed at the same time, the line conductors would be short-circuited via the star point. The delta contactor must also never switch on together with the line contactor. Mutual interlocking in the control circuit prevents both speed steps from being switched on at the same time.

Which efficiency class must pole-changing motors meet?

None is mandatory. The Ecodesign Regulation (EU) 2019/1781 exempts motors with multiple speeds from its efficiency requirements, while single-speed motors from 0.75 to 1,000 kW must in principle achieve at least IE3 since July 2021.

How do you protect pole-changing motors against overheating?

With overload protection matched to the rated current of the step that is currently active, and with PTC thermistors according to DIN 44081 and DIN 44082 in the winding. The thermistors measure the winding temperature directly and thus also provide protection in the low step, in which a self-ventilated motor receives less cooling air.

Sources

  1. Wikipedia (DE): Drehstrom-Asynchronmaschine (three-phase asynchronous machine)
  2. University of Rostock, Institute of Electrical Power Engineering (DE): Part 3 Asynchronous machines
  3. Wikipedia (EN): Dahlander pole changing motor
  4. Wikipedia (DE): Kreiselpumpe (centrifugal pump)
  5. Wikipedia (DE): Motorschutz (motor protection)
  6. Official Journal of the European Union (DE): Commission Regulation (EU) 2019/1781 laying down ecodesign requirements for electric motors and variable speed drives