230V motor with speed control: when a frequency converter, phase-angle control or winding taps are the right fit, and where capacitor motors reach their limits.
AI This article was created with the help of AI.
Table of contents
- Which 230V motors are suitable for speed control
- Phase-angle speed controllers: possibilities and limits
- 230 V frequency converter: stepless speed control
- Capacitor motor: speed, direction of rotation and capacitor
- Sizing, cooling and EMC in converter operation
- Speed control in the drive train
- Frequently asked questions
- Sources
Which 230V motors are suitable for speed control
If you are looking for a 230V motor with speed control, you should first determine the motor type. Three designs mainly operate on the single-phase 230 V supply: capacitor motors, universal motors and shaded-pole motors. In addition, there is the three-phase motor, which can also be operated on 230 V via a frequency converter. Each design can be adjusted in speed in a different way and to a different degree.
The capacitor motor is an asynchronous motor with a squirrel-cage rotor that is fed with single-phase alternating current; a capacitor generates the auxiliary phase required for the rotating field. Its dimensioning is optimized for a single load case of speed and torque; to change the speed, windings have to be switched over[1]. The universal motor, by contrast, is a series-wound motor with a commutator and carbon brushes. It is built up to a rated power of 3 kW and with rated speeds of 3,000 to 30,000 rpm; its speed is highly load-dependent[2]. Shaded-pole motors are simple, inexpensive drives up to about 300 W with an efficiency of around 30 % and are the standard drive for small fans[3].
| Motor type on the 230 V supply | Speed adjusted via | Suitability and limits |
|---|---|---|
| Three-phase motor on a single-phase-fed frequency converter | Frequency and voltage (V/f, vector control) | stepless, torque approximately constant up to rated speed; standard approach for new designs |
| Universal motor (carbon brushes) | Phase-angle control | finely adjustable, but load-dependent speed and brush wear |
| Capacitor motor | Winding taps, voltage control, converters for capacitor motors | limited; voltage control mainly for fans, no higher starting torque |
| Shaded-pole motor | Cross-pole connection, voltage control for fans, converters to a limited extent | small power ratings only, low efficiency |
The basis of any control is the relationship between frequency and speed: an asynchronous motor on the mains rotates at a fixed speed that depends on the number of pole pairs and the supply frequency[4]. At 50 Hz, a 4-pole motor has a synchronous speed of 1,500 rpm; depending on the load, the mechanical speed is usually 1 to 8 % lower[5]. If you want to vary the speed over a wide range, you therefore have to change the frequency.
Phase-angle speed controllers: possibilities and limits
Simple speed controllers for 230 V motors work like a dimmer with phase-angle control. A triac switches on the current in each half-wave only with a delay after the zero crossing; the later it fires, the lower the average power. The motor receives a non-sinusoidal voltage at an unchanged frequency.
For the universal motor, this is the usual solution: phase-angle control allows practically loss-free and finely graduated speed control, because torque and speed change with the RMS value of current and voltage[2]. Universal motors are typically found in handheld devices such as drills and hand mixers[2].
With capacitor and shaded-pole motors, the situation is different. In asynchronous motors, the torque decreases quadratically as the voltage drops. The motor therefore only runs noticeably slower if the load torque also decreases sharply with speed, as with fans. With many fans, the speed can be reduced by lowering the voltage electronically or with a transformer. With phase-angle control, however, electromagnetic excitation in the motor can lead to resonances and disturbing noise. Only motors with a soft characteristic can be speed-controlled via the voltage, motors with a stiff characteristic only via the frequency; in addition, voltage control reduces power consumption considerably less than a frequency converter[6].
For conveyor belts, agitators or hoist drives with approximately constant load torque, a dimmer therefore does not provide speed control: the torque collapses, the slip increases and the motor heats up without stably holding the desired speed.
230 V frequency converter: stepless speed control
A frequency converter rectifies the mains voltage, smooths it in the DC link and, in the inverter, uses pulse-width modulation to generate a voltage of variable magnitude and frequency. Depending on the design, it is fed with single-phase or three-phase AC voltage and generates a three-phase AC voltage from it for three-phase motors[4]. This allows a three-phase motor to reach speeds from almost zero up to rated speed steplessly, without the torque dropping. Above the rated frequency, in the field-weakening range, the output torque decreases[4].
On the 230 V single-phase supply, the combination of a single-phase-fed converter and a three-phase motor is therefore the robust solution for speed control. A motor with the nameplate 230 V Δ / 400 V Y is connected in delta for this purpose, so that each winding receives the output voltage of 230 V. The capacitor and starting switch are no longer needed.
The simplest operating mode is V/f operation: up to the rated frequency, the converter keeps voltage and frequency in a constant ratio, i.e. 4.6 V/Hz at 230 V and 50 Hz. This results in constant torque over wide ranges without overloading the motor in terms of current. At very low speeds, the torque drops due to the ohmic winding resistance; an adjustable voltage increase (boost) compensates for this. In V/f operation, the speed fluctuates with the load. Slip compensation, a speed encoder or vector control, which works with a motor model, ensure a constant speed[4].
There are also single-phase frequency converters for capacitor motors that require no changes to the motor, for example for existing pumps, fans, bench drills or conveyor belts. They first run the motor up at rated frequency and then reduce the frequency, because the capacitor only generates the auxiliary phase for starting at rated frequency. A higher starting torque is not possible this way; shaded-pole motors can only be operated like this with restrictions[4]. For new installations, the three-phase motor remains the better choice, especially since capacitor motors in the upper power range are increasingly being replaced by three-phase motors as converters become more and more affordable[1].
Capacitor motor: speed, direction of rotation and capacitor
In a capacitor motor, one stator winding is connected directly to the mains, while the second winding, offset by 90°, is connected in series with a capacitor. The rotating field generated in this way is load-dependent and results in a low starting torque. An additional starting capacitor, about 2 to 3 times as large, which is connected in parallel during start-up, increases the starting torque. With optimal capacitor sizing, the motor achieves about 65 % of the mechanical power of a three-phase motor of comparable size[1]. How to determine the capacitance is shown in our article on capacitor motor calculation.
In a capacitor motor, fixed speed steps are created by switching windings[1]; it can only be controlled steplessly with the restrictions described. In shaded-pole motors, a speed change is implemented via the so-called cross-pole connection[3].
Another frequent question is how to change the direction of rotation of a 230V motor with a capacitor. Cost-optimized capacitor motors with a main and auxiliary winding are designed for one direction of rotation only; the windings are then not interchangeable. Motors with two identical windings, on the other hand, can be reversed with a single-pole changeover switch, which must have a delay between the switch positions to avoid an arc[1]. In motors whose winding ends are brought out individually in the terminal box, reconnecting the auxiliary winding reverses the direction of rotation. We explain the terminal assignment and typical wiring mistakes in the article 230V motor with capacitor: circuit diagram. On a frequency converter, the direction of rotation of the three-phase motor can be reversed electronically[5].
Sizing, cooling and EMC in converter operation
The decisive factor when selecting the converter is the motor current: the output current of the device must permanently cover the rated current of the motor and provide a reserve for start-up or load peaks. How to determine this value is shown in our article on the rated current of motors. During commissioning, the nameplate data, i.e. rated current, voltage, frequency and speed, are entered into the converter. Vector control stores the motor parameters in a motor model in the converter or determines them automatically[4].
A self-ventilated motor cools less effectively at low speed. In continuous operation at low frequency, it can therefore only deliver approximately its rated torque, because the rotor and stator are not sufficiently cooled[5]. In industry, slow-running motors are cooled by forced-ventilation fans whose speed depends on the mains and not on the converter[4]. A temperature sensor in the winding, such as a PTC thermistor evaluated by the converter, detects the heating directly. A purely current-dependent motor protection device, on the other hand, does not detect the poorer cooling, because the motor current does not rise in this case.
- EMC: converters generate strong interference signals on the motor supply cable. The cable is shielded and the shield is connected over a large area at both ends; a sine-wave filter between the converter and the motor provides further mitigation[4].
- Cable length: even a low-capacitance, shielded motor cable must not exceed a certain length, for example 20 m; longer cables lead to reflections that stress the motor insulation[4].
- Switching frequency: a pulse frequency above 16 kHz avoids audible noise, but increases the losses in the converter, worsens EMC and increases the stress on the motor[4].
- Bearings: currents through the motor bearings can cause electrical erosion; motors for converter operation are selected in accordance with DIN VDE 0530-25[4].
The effort pays off especially with pumps and fans: if the volume flow is halved, the required torque drops to 25 % and the drive power to one eighth of the rated power[4].
Speed control in the drive train
Whether winding tap, phase-angle control or converter: the decision depends on the driven machine. Fans with a quadratic load torque often manage with voltage control, while drives with constant torque such as conveyors, dosing or winding drives need frequency control. For individually operated fans, motors with an integrated frequency converter offer advantages in price and installation space in many cases[6]. The same principle applies to gear motors in which the motor, converter and gearbox form a compact unit.
If a low output speed is required, a gearbox is usually the better solution than a motor that runs permanently at a very low frequency: the motor stays in the well-cooled speed range, and the gearbox increases the torque. Which 230 V motors and gearboxes are suitable for this is shown in our overview of the 230V gear motor. As a supplier for the complete drive train, we at ATEK Drive Solutions design the motor, gearbox and brake to fit precisely from a single source, including for operation on a frequency converter. You can find an overview of our IEC standard motors in our product range, and we will be happy to advise you personally on your specific application via our contact page.
Frequently asked questions
Can I use a dimmer as a speed controller for a 230V motor?
Only for the universal motor with carbon brushes is a phase-angle controller the usual solution. For capacitor and shaded-pole motors, voltage control is at best suitable for fans whose load torque drops sharply with speed, and even there noise can occur. For drives with constant torque, a frequency converter is necessary.
Can a capacitor motor be controlled with a frequency converter?
Yes, with special single-phase converters for capacitor motors. They run the motor up at rated frequency and then reduce the frequency; they do not increase the starting torque. For new designs, a three-phase motor on a single-phase-fed converter is the more robust solution.
How do I change the direction of rotation of a 230V motor with a capacitor?
Only motors whose windings are designed for this can be reversed: by reconnecting the auxiliary winding or, with two identical windings, via a changeover switch with a delay. Cost-optimized motors are often built for one direction of rotation only. The circuit diagram in the terminal box is decisive.
What does V/f control mean for a frequency converter?
Up to the rated frequency, the converter keeps voltage and frequency in a fixed ratio, i.e. 4.6 V/Hz at 230 V and 50 Hz. This keeps the torque constant over wide ranges. At very low speeds, a boost raises the voltage; slip compensation or vector control provide a constant speed under changing load.
Why does my motor get hot at low speed?
The fan on the motor shaft turns more slowly and delivers less cooling air. In continuous operation at low frequency, the motor can therefore only deliver approximately its rated torque. Remedies include a forced-ventilation fan, a gear reduction that keeps the motor in the higher speed range, and a temperature sensor evaluated by the converter.
Can speed control be retrofitted, for example on a mitre saw or pool pump?
That depends on the motor type on the nameplate. Saws with a universal motor can be fitted with a phase-angle controller. Pumps with a capacitor motor need a converter that is approved for capacitor motors; there, the auxiliary phase is only generated at rated frequency.
How do I control the speed of a 400 V three-phase motor?
With a frequency converter. On the 400 V three-phase supply, a three-phase-fed device is used; on the 230 V single-phase supply, a single-phase-fed device with a 3 × 230 V output is used; the motor with the nameplate 230 V Δ / 400 V Y is then connected in delta.
How large does the frequency converter for a 230V motor need to be?
The output current is decisive: it must at least cover the rated current of the motor and provide a reserve for start-up and load peaks. The power rating alone is not sufficient for the selection.
Sources
- Wikipedia (DE): Kondensatormotor (capacitor motor)
- Wikipedia (DE): Einphasen-Reihenschlussmotor (universal motor)
- Wikipedia (DE): Spaltpolmotor (shaded-pole motor)
- Wikipedia (DE): Frequenzumrichter (frequency converter)
- Wikipedia (DE): Drehstrom-Asynchronmaschine (three-phase asynchronous machine)
- DIE KÄLTE & Klimatechnik 2/2007 (DE): Methods for changing the speed of fans in refrigeration technology