What the service factor of gearboxes means, how load classification, running time and switching frequency determine it, and how to calculate it using an example.
AI This article was created with the help of AI.
Table of contents
- What the service factor of gearboxes means
- Load classification of the driving and driven machine
- Running time, switching frequency and type of drive
- Calculating the service factor: conveyor system example
- Operating factor, service factor and motor service factor
- Avoiding design errors
- Frequently asked questions
- Sources
What the service factor of gearboxes means
The service factor is the allowance by which you multiply the rated torque of an application before selecting a gearbox. In gear calculation, the same quantity is called the application factor KA; operating factor is the common alternative name[1]. In gearbox catalogues, you will also find it as fB, fs, operating factor or gearbox coefficient. DIN 3990 and ISO 6336 define KA as a factor on the nominal load that covers all additional loads entering the gearing from outside[2]. These additional loads depend on the driving and driven machine, on the masses and spring stiffnesses in the input and output train, and on the operating conditions[3].
A simple rule applies to the selection: the rated torque of the gearbox must be at least as large as the load torque at the output multiplied by the service factor. Read the other way round: with a required service factor of 1.5, a gearbox with a rated torque of 100 Nm is suitable for load torques up to around 67 Nm.
Behind the factor lies a service life calculation. According to the more precise method A, KA is determined from measured or calculated load spectra: an equivalent torque combines the varying load spectrum into a single load according to the Palmgren-Miner damage accumulation rule, and the ratio of this torque to the rated torque is the application factor. A gearbox loaded with KA times the rated torque theoretically achieves the same service life as in real operation with fluctuating load[2]. The service factor is therefore not a blanket overload reserve; it represents the stress over the entire period of use.
Load classification of the driving and driven machine
If no load measurements are available, DIN 3990 and ISO 6336 provide guide values. They depend on the operating characteristics of the driving and the driven machine and lie approximately in the range 1.0 ≤ KA ≤ 2.25[2]. Four load classifications are distinguished, which combine to form the following matrix[3]:
| Driving machine \ driven machine | uniform | light shocks | moderate shocks | heavy shocks |
|---|---|---|---|---|
| uniform | 1.00 | 1.25 | 1.50 | 1.75 |
| light shocks | 1.10 | 1.35 | 1.60 | 1.85 |
| moderate shocks | 1.25 | 1.50 | 1.75 | 2.00 |
| heavy shocks | 1.50 | 1.75 | 2.00 | ≥ 2.25 |
The table only provides rough indications. A KA derived from measured load spectra or from a comprehensive system analysis based on proven operating experience is more precise[3]. Guide values from the machine elements literature help with classifying typical machines[4]:
| Load class | KA | Examples |
|---|---|---|
| uniform to light shocks | 1.0 to 1.1 | electric motor with uniform operation and infrequent starting, uniformly loaded belt conveyors, packaging machines, feed drives of machine tools, fans |
| light to medium shocks | 1.2 to 1.5 | three-phase motor with frequent starting, main drives of machine tools, conveyor systems for unit loads, centrifugal pumps, gear pumps |
| moderate shocks | 1.5 to 2 | woodworking machines, light ball mills, multi-cylinder piston pumps, industrial fans with frequent starting |
| heavy shocks | 2 to 3 | excavators, heavy ball mills, crushers for stone and ore, mechanical hammers |
A uniformly loaded conveyor belt is therefore at the lower end, a stone crusher at 2 to 3. The actual operating characteristics are decisive: the same machine can move up one class with uneven loading or frequent starting. How torque peaks arise when tensioning and starting belts is described in our article on conveyor belt tension.
Running time, switching frequency and type of drive
In addition to the load classification, two operating variables determine the factor: the daily running time and the number of switching operations per hour. Gearbox manufacturers combine both in tables or diagrams in their catalogues, usually graded by hours of running time per day and switching operations per hour. These values are manufacturer-specific and cannot simply be transferred from one catalogue to another. The standards also permit other values if the purchaser and the manufacturer agree on them[2].
Running time: Tooth flanks and bearings fatigue with the number of load cycles. The service life calculation is therefore based on the S-N curve (Wöhler curve) of the material and the Palmgren-Miner damage accumulation[2]. A plant in three-shift operation accumulates many times the load cycles per year of a machine that runs two hours a day and, with the same service life expectation, needs a higher service factor.
Switching frequency: When an electric motor is switched on directly, the torque increases by up to 3 times. It puts a sudden load on the machine and shortens its service life[5]. Every start, every braking operation and every reversal of the direction of rotation brings such a peak into the gearbox. Cycling drives with many starts per hour therefore need a higher factor than the same drive with few switching operations.
Type of drive: How harsh the starts are depends on the starting method. A soft starter ramps the voltage steplessly during the starting phase and thus prevents, among other things, gear tooth flanks from striking each other in the gearbox[5]. For a reliable design, you should therefore record:
- load torque and output speed in normal operation as well as the highest torque during operation
- daily running time and planned service life in operating hours
- starts, braking operations and reversing operations per hour
- starting method: direct-on-line, star-delta, soft starter or frequency converter
- mass moment of inertia of the driven machine and ambient temperature
Calculating the service factor: conveyor system example
A worked example shows the procedure. A conveyor system for unit loads requires 3 kW at 60 rpm at the output. It runs in two-shift operation; the three-phase motor starts direct-on-line and several times per hour.
- Determine the load torque: M = 9550 × P / n = 9550 × 3 kW / 60 rpm = 477.5 Nm.
- Determine the load classification: The literature table lists the three-phase motor with frequent starting and the conveyor system for unit loads under light to medium shocks[4]. In the matrix, we therefore classify both the driving and the driven machine as light shocks; this gives KA = 1.35[3].
- Check running time and switching operations: If your gearbox manufacturer’s table value for 16 hours per day and the planned number of switching operations is higher, the higher value applies.
- Required rated gearbox torque: 477.5 Nm × 1.35 ≈ 645 Nm.
- Check the gear motor: A 3 kW gear motor with 60 rpm delivers 477.5 Nm at the output. If its gearbox has a rated torque of 700 Nm, the actual service factor is 700 / 477.5 ≈ 1.47. This is above the required value of 1.35, so the selection is suitable.
| Quantity | Formula | Example value |
|---|---|---|
| Load torque at the output | M = 9550 × P / n | 477.5 Nm |
| required service factor | from load classification, running time, switching operations | 1.35 |
| required rated gearbox torque | M × fB, required | ≈ 645 Nm |
| actual service factor | rated gearbox torque / output torque of the motor | ≈ 1.47 |
If you do not know the actual load torque, calculate with the output torque of the motor at rated power. This is on the safe side. With high gear ratios, the torque is distributed over several stages, whose design we explain in our article on multi-stage spur gearboxes.
Operating factor, service factor and motor service factor
For gearboxes, “service factor” is usually just the English term for the German “Betriebsfaktor” (operating factor). The American gearing standard AGMA 2101 uses an overload factor KO instead of KA. If no better data are available, application factors according to DIN 3990 or ISO 6336 can also be used as KO[2].
More important is the distinction between two values that both appear as the service factor in catalogues:
- Required service factor: It results from the application, i.e. from the load classification, running time and switching frequency.
- Actual service factor of a gear motor: It is the ratio of the rated gearbox torque to the output torque of the motor. It must be at least as large as the required value.
A gear motor with a high actual factor can nevertheless fail prematurely if the required factor for a shock load was set too low. A third parameter is the service factor of an electric motor, which people often search for as “motor service factor”. It is defined in the American standard ANSI/NEMA MG 1 and is a multiplier on the rated power that the motor may deliver temporarily. Values between 1.15 and 1.4 are typical. Every hour of operation in the service factor range costs two to three hours of service life at rated power, and there is no IEC standard for the service factor[6]. The motor service factor therefore says nothing about whether the downstream gearbox can carry the application permanently.
Avoiding design errors
A service factor that is set too low overloads the gearing and bearings in the long term, even if the gearbox runs inconspicuously in normal operation. A factor that is too high across the board, on the other hand, leads to unnecessarily large gearboxes: anyone who simply uses the ratio of peak to rated torque instead of KA is always on the safe side but risks unnecessarily large gearboxes[2]. You should check these points in the design:
- classify the operating characteristics realistically, including for special conditions such as starting under load or blocking
- use the actual running time, not the running time from the original specification, if the plant now runs longer
- include braking and reversing operations in the switching operations
- with worm gearboxes, also check the thermal capacity in continuous operation
- use factors only from the catalogue of the manufacturer whose gearboxes you use
The service factor always acts in combination with the motor, starting method and gear ratio. As a supplier for the complete drive train, we at ATEK Drive Solutions design gearbox and motor to fit precisely from a single source, from the standard gearbox to the customer-specific solution. You will find an overview in our gearbox range. For the design of your application, you can reach our application engineering team via our contact page.
Frequently asked questions
What is the service factor of a gear motor?
For a gear motor, the actual service factor is the ratio of the rated gearbox torque to the output torque of the motor. It must be at least as large as the service factor that your application requires based on load classification, running time and switching frequency.
What does the application factor KA mean?
KA is the designation of the service factor in gear calculation according to DIN 3990 and ISO 6336. It covers all additional loads that enter the gearing from outside, for example due to shocks, starting processes or vibrations. Depending on the driving and driven machine, the guide values range from 1.0 to 2.25.
May the service factor be less than 1?
The guide values according to DIN 3990 and ISO 6336 start at 1.0 for a uniform drive and a uniform driven machine. Different values are only permissible if the purchaser and the manufacturer agree on them. Without the express approval of the gearbox manufacturer, you should not go below 1.0.
Is a higher service factor always better?
No. A factor that is too high leads to larger, heavier and more expensive gearboxes without the application requiring it. The aim is a factor that represents the actual stress over the planned service life.
What is the difference between the operating factor and the service factor?
For gearboxes, both terms mean the same allowance; service factor is the English term. For electric motors, on the other hand, the service factor according to NEMA denotes a temporarily permissible power reserve, usually 1.15 to 1.4. It has nothing to do with gearbox design.
Which service factor applies to a conveyor belt or a crusher?
According to literature values, a uniformly loaded conveyor belt with an infrequently starting electric motor is at 1.0 to 1.1, and unit load conveyors with frequent starting at 1.2 to 1.5. Crushers for stone and ore belong to the heavy shocks with 2 to 3. Running time and switching frequency can increase the value further.
How do you select the right gearbox?
Determine the load torque and output speed, determine the required service factor from load classification, running time and switching frequency, and multiply the two. The rated gearbox torque must reach at least this value. Then check the gear ratio, design, shaft load and, for worm gearboxes, the thermal limit.
Does the type of gearbox play a role in the service factor?
Yes. The manufacturer tables differ depending on the type of gearbox, and with worm gearboxes, heating in continuous operation must be considered in addition to torque. Therefore, always use the factors from the catalogue of the gearbox you are using.
Sources
- Anhalt University of Applied Sciences (DE): Calculation principles for spur gears (fatigue strength verification for gearing)
- Gear Technology, May 2019: Determining value of Ka in regards to DIN 3990 and AGMA standards
- Forschungsvereinigung Antriebstechnik (FVA) (DE): Anwendungsfaktor (application factor)
- Online manual for machine element calculation (DE): guide values for application factors according to Niemann, Winter, Höhn, Maschinenelemente, Volume 1 (3rd edition 2001, Fig. 1.11)
- ZVEI (DE): Motoren starten – Ressourcen schonen (Starting motors – conserving resources)
- Wikipedia (EN): Power rating (Service factor)