Explosion-proof motor: what ATEX requires

An explosion-proof motor, Ex motor or ATEX motor for short, is an electric motor that must not form an effective ignition source in a hazardous zone. For this purpose, the housing, terminal box and winding protection are designed and tested to a type of protection. The framework is set by two EU directives: since 20 April 2016, the product directive 2014/34/EU has obliged manufacturers to carry out conformity assessment procedures, and the operating directive 1999/92/EC obliges the operator to classify zones and to draw up an explosion protection document[1].

The zone determines the equipment category that the motor must meet as a minimum[2]:

Zone gas / dustExplosive atmosphereEquipment categoryProtection level (EPL)
Zone 0 / Zone 20continuously, for long periods or frequently1G / 1DGa / Da
Zone 1 / Zone 21occasionally in normal operation2G / 2DGb / Db
Zone 2 / Zone 22normally not in normal operation, otherwise only rarely and for a short time3G / 3DGc / Dc

A category 2 motor must not become an ignition source either in undisturbed operation or in the event of probable faults such as overload or a locked rotor[3]. For category 3 equipment in zone 2, the manufacturer can issue the declaration of conformity itself[4]. What zones look like at silos and bulk material plants is shown in our article on explosion-proof geared motors for silo systems.

Types of protection and marking of Ex motors

The type of protection describes the principle by which the motor prevents ignition. For electric motors, five types mainly come into question:

SymbolPrincipleUseStandard
Ex denclosure withstands an internal explosion, flameproof gaps at all openingscategory 2G and 3GEN 60079-1
Ex ebno sparks and no impermissible temperatures, even with foreseeable faultscategory 2G and 3GEN 60079-7
Ex eclike increased safety in normal operation, fault condition not consideredzone 2 (category 3)EN 60079-7
Ex poverpressure with protective gas, monitored supply, pre-purgingcategory 2G and 3GEN 60079-2
Ex tdust-protected (IP5X) or dust-tight (IP6X) enclosure, limited surface temperaturecategory 1D, 2D and 3DEN 60079-31

With Ex d, the surface temperature must remain below the ignition temperature even in the event of an expected fault[5]. Ex ec has replaced the former type of protection nA since the 2015 edition of EN 60079-7; according to the PTB, with type of protection n on electrical machines in duty types S1 and S2, starting and the locked condition do not have to be considered[4]. Ex p needs a monitored protective gas supply[6] and is used mainly for higher-power equipment such as large motors, Ex e often for terminal boxes and squirrel-cage motors[2].

The rating plate carries a marking for this, for example “Ex e IIC T4 Gb”: increased safety, explosion group IIC, temperature class T4, protection level Gb for zone 1. The six temperature classes range from T1 with 450 °C to T6 with 85 °C maximum surface temperature; T4 is at 135 °C. IIC is the most hazardous gas group[2]. For dust, the marking gives the maximum surface temperature directly instead of the class, for example “II 2 D Ex tb IIIC T120 °C Db”[7].

The terminal box: Ex e or Ex d

The terminal box, also called connection box, is permanently attached to the motor and is part of its type of protection. In the Ex de combination, the motor housing has a flameproof enclosure, and the type of protection increased safety “e” applies to the terminal box[8]. In an Ex e box, an explosive atmosphere may enter; ignition is prevented by the fact that neither impermissible temperatures nor sparks occur, in normal operation as well as with foreseeable faults[9]. If the terminal box also has a flameproof enclosure, the Ex d principle applies: an explosion inside is contained, and all openings need flameproof gaps[5].

You should therefore check whether terminals and entries suit your wiring, and use only cable entries and blanking plugs that the operating instructions and certificate permit. With the type of protection Ex t, the enclosure including the terminal box must be dust-protected (IP5X) or dust-tight (IP6X)[7]. Deposited dust also counts: for layers of up to 5 mm, the maximum surface temperature must be at least 75 K below the glow temperature of the dust; for thicker layers, the permissible value drops considerably[10]. Plan cleaning intervals accordingly.

Motor protection, tE time and frequency converter

With an Ex e motor, overload protection is essential for explosion protection; the monitoring devices must have been function-tested[9]. Two concepts are common: a motor protection switch with current-dependent delay, or direct temperature monitoring with PTC thermistors in the winding. With protection via the overcurrent release, the tE time, the maximum locked-rotor time of the motor, is decisive for the locked rotor. Because the rotor is difficult to monitor, the PTC thermistor alone is often not sufficient for larger machines, for example from 132 mm shaft height; it then supplements a motor protection switch that must be used. After a trip, a sufficient cooling time must also be observed before switching back on[3].

With a flameproof motor as well, the temperature class, so 135 °C for T4, must be maintained in the event of a fault such as a locked rotor. If the type-examination certificate prescribes a protective device, it must be certified under Directive 2014/34/EU; the tripping device for PTC thermistors must be type-examined. If it is located in the control cabinet outside the Ex zone, approval as a safety device is sufficient[8].

On a frequency converter, the cooling changes: self-ventilated motors are cooled less well at controlled speed. According to a procedure developed by the PTB for Ex e motors, only the motor is approved; its type-examination certificate determines the thermal monitoring, in addition to the certified PTC thermistor evaluation a speed-dependent current limitation[11]. The type-examination certificate of the motor is therefore decisive.

Gearboxes and brakes in the Ex area

The ATEX product directive 2014/34/EU also covers non-electrical equipment, such as rotating couplings, which can develop into ignition sources through impermissibly high heating[1]. For explosion-protected mechanical equipment such as gearboxes, the standards ISO 80079-36 and ISO 80079-37 apply, with the types of protection constructional safety “c”, control of ignition sources “b” and liquid immersion “k”. On the rating plate, all non-electrical equipment carries the identifying letter “h”, without separate indication of c, b or k. Together with the IEC 60079 series of standards, these standards form an international set of rules; like the electrical equipment, they are also to be integrated into the IECEx system for Ex equipment used internationally[12].

For the drive train, it follows that the gearbox, coupling and brake, just like the motor, must meet the equipment category of the zone and maintain the required temperature class. Which brakes are suitable for Ex zones is covered in our article on ATEX brakes.

Inspection, repair and selection

The German Ordinance on Industrial Safety and Health (Betriebssicherheitsverordnung) requires an explosion safety inspection before first commissioning. This inspection concerns the installation; it does not replace the certificate of the individual device. The installation must be inspected periodically at least every six years, and equipment within the meaning of Directive 2014/34/EU at least every three years. After the repair of a part on which explosion protection depends, the motor may only be put back into operation after an inspection, unless the manufacturer inspects and confirms this itself[13]. Inspection and maintenance in operation are governed by DIN EN IEC 60079-17; repair, overhaul and reclamation are excluded there[14]. DIN EN IEC 60079-19 applies to these, the content of which relates largely to rotating electrical machines[15].

Under the Ecodesign Regulation, Ex eb motors have had to reach at least IE2 since July 2023, and other three-phase motors from 0.75 to 1,000 kW at least IE3; explosion-proof motors are exempt from the IE4 requirement for 75 to 200 kW[16].

To select your Ex motor, we need the following information:

  • zone, equipment category and explosion group, gas or dust
  • temperature class or maximum surface temperature
  • power, speed, duty type, mains or converter operation
  • design of the terminal box and cable entries

As a supplier of the complete drive train, at ATEK Drive Solutions we size motor, gearbox and brake to fit together from a single source, matched to zone, temperature class and duty type. You will find an overview of our IEC motors in the product range; for your application, we are happy to advise you via our contact page.

Frequently asked questions

What is an explosion-proof motor?

An electric motor that does not form an effective ignition source in a hazardous zone. It is built and tested to a type of protection from the IEC 60079 series of standards, for example Ex d, Ex e or Ex t, and marked for an equipment category, explosion group and temperature class. In everyday language, it is also called an Ex motor or ATEX motor.

What is the difference between Ex d, Ex e and Ex de?

Ex d contains an explosion in the enclosure and uses flameproof gaps to prevent it from spreading outside. Ex e prevents the formation of sparks and impermissible temperatures in the first place. Ex de combines both: flameproof motor, terminal box with increased safety.

Which Ex motor is permitted for zone 1, zone 2 or zone 21?

Zone 1 requires at least category 2G, for example Ex d or Ex eb. Zone 2 requires at least category 3G; here Ex ec, for example, is sufficient. Zone 21 requires category 2D, for example protection by enclosure in the Ex tb design.

May an Ex motor be operated on a frequency converter?

That is determined by the type-examination certificate of the motor. According to the PTB procedure for Ex e motors described in 2010, it requires, in addition to the certified PTC thermistor evaluation, a speed-dependent current limitation, because the internal fan cools less at low speed.

What does the tE time mean?

The tE time is the maximum locked-rotor time of an Ex e motor. The overcurrent release of the motor protection switch is matched to it so that the motor switches off with a locked rotor before impermissible temperatures occur.

Which temperature class does my motor need?

A temperature class whose maximum surface temperature is below the ignition temperature of the gases or vapours at the place of use. T4, for example, allows a maximum of 135 °C, T6 a maximum of 85 °C. For dust, the stated maximum surface temperature counts in relation to the minimum ignition and glow temperature of the dust.

How often does an Ex motor have to be inspected, and who repairs it?

Under the Ordinance on Industrial Safety and Health, equipment within the meaning of Directive 2014/34/EU must be inspected at least every three years, and the installation at least every six years. Repair, overhaul and reclamation are covered by DIN EN IEC 60079-19; after the repair of a part relevant to explosion protection, an inspection by a person who is officially recognised for this purpose and qualified to carry out the inspection is required, unless the manufacturer inspects and confirms it itself.

Are there explosion-proof motors in IE3 or IE4?

The Ecodesign Regulation requires at least IE2 for Ex eb motors; most other three-phase motors from 0.75 to 1,000 kW, including those with other types of protection, must reach IE3. The IE4 requirement for 75 to 200 kW, by contrast, does not apply to explosion-proof motors.

Sources

  1. Wikipedia (DE): ATEX
  2. Wikipedia (DE): Explosionsschutz (explosion protection)
  3. PTB (DE) (Lehrmann, Dreger): Ein Ansatz zur Festlegung der Sperrzeiten nach einer Motorschutzauslösung bei explosionsgeschützten Antrieben (an approach to determining lock-out times after a motor protection trip in explosion-protected drives), 15th BAM-PTB Colloquium 2019
  4. PTB (DE): Zündschutzart n (type of protection n)
  5. PTB (DE): Druckfeste Kapselung – Ex d (flameproof enclosure – Ex d)
  6. PTB (DE): Überdruckkapselung – Ex p (pressurised enclosure – Ex p)
  7. PTB (DE): Schutz durch Gehäuse – Ex t (protection by enclosure – Ex t)
  8. KomNet NRW (DE): Motorschutzschalter für druckfest gekapselte Motoren (motor protection switches for flameproof motors) (Dialog 44264)
  9. PTB (DE): Erhöhte Sicherheit – Ex e (increased safety – Ex e)
  10. BG RCI (DE): Anforderungen des Staubexplosionsschutzes an die Oberflächentemperatur von Geräten (requirements of dust explosion protection for the surface temperature of equipment)
  11. CHEManager (DE): Neues Explosionsschutzkonzept (new explosion protection concept) (2010)
  12. PTB/BAM (DE) (Beyer, Grätz): ISO 80079-36 und -37 – Die neuen internationalen Normen für explosionsgeschützte mechanische Geräte (the new international standards for explosion-protected mechanical equipment)
  13. Betriebssicherheitsverordnung (DE), Anhang 2 (Ordinance on Industrial Safety and Health, Annex 2)
  14. DIN Media (DE): DIN EN IEC 60079-17
  15. DIN Media (DE): DIN EN IEC 60079-19
  16. Verordnung (EU) 2019/1781 (DE), Anhang I (Regulation (EU) 2019/1781, Annex I)