Calculating electric motor power with P = M · n / 9550: shaft power, efficiency, nameplate, sizing for a load, application factor and IE classes.

AI This article was created with the help of AI.

Calculating electric motor power: the formula

The power of an electric motor is the mechanical power at its shaft. In a rotary motion, it is the product of torque and angular velocity: P = M · ω = 2π · n · M. Together with the speed, the torque at the drive shaft determines the mechanical power delivered by a motor[1]. With M in newton metres and n in revolutions per second, you get the power in watts.

In drive technology, speed is specified in revolutions per minute. This results in the numerical value equation P = M · n / 9550 with P in kW, M in Nm and n in rpm. The constant results from 60 · 1000 / 2π ≈ 9549 and is usually rounded to 9550. Rearranged, you get the torque from the power: M ≈ 9549 · P / n[2].

MotionQuantitiesFormulaExample
Rotary motionTorque M (Nm), speed n (rpm)P = M · n / 9550 (kW)120 Nm at 95.5 rpm gives 1.2 kW
Torque from powerPower P (kW), speed n (rpm)M = 9550 · P / n (Nm)5.5 kW at 1,450 rpm gives around 36 Nm
Linear motionForce F (N), velocity v (m/s)P = F · v (W)Lifting 500 kg at 0.5 m/s: 4,905 N · 0.5 m/s ≈ 2.45 kW

Older data sheets sometimes state the power in PS (metric horsepower). One metric horsepower corresponds to 735.49875 W; rounded, 1 kW ≈ 1.36 PS. The Anglo-American horsepower is slightly larger at around 745.7 W[3]. For imported machines, you should therefore check which unit is meant.

Output power and input power

The nameplate of a motor shows the rated power. It is the delivered mechanical shaft power Pout. The associated rated torque is usually not stated on the nameplate; you calculate it from rated power and rated speed[2]. The power Pin drawn from the grid is greater, because copper, iron and friction losses occur in the motor.

The ratio of the two quantities is the efficiency η = Pout / Pin; the difference between supplied and delivered power is the power loss[4]. It is converted almost entirely into heat, which the motor must dissipate via the housing and fan. An example: a four-pole 11 kW motor at the IE3 minimum efficiency of 91.4 %[5] consumes 11 kW / 0.914 ≈ 12.0 kW. Around 1.0 kW is lost as waste heat.

ParameterFormulaSignificance for sizing
Shaft power PoutP = M · n / 9550Rated power on the nameplate, basis for gearbox and driven machine
Input power PinPin = Pout / ηelectrical connected load, basis for grid, cable and protective devices
Power loss PLPL = Pin − PoutWaste heat that must be dissipated via the housing and cooling
Efficiency ηη = Pout / Pincharacterizes the efficiency of the motor

The input power of a running three-phase motor can also be determined from measured values: P = √3 · U · I · cos φ, with the average of the three line voltages and currents[6]. We explain the electrical side with active, reactive and apparent power in detail in the article Calculating three-phase power.

Sizing motor power for a load

If you want to calculate the drive power, you do not start with the motor, but with the driven machine. Only the torque required there and the required speed determine the motor power. If there is a gearbox, a coupling or a belt drive between the motor and the load, their individual efficiencies are multiplied to give the overall efficiency[4]. The motor must deliver the load power divided by this overall efficiency.

A worked example for a rotary table that requires 120 Nm at 95.5 rpm at the output shaft:

  • Step 1, load power: P = 120 Nm · 95.5 rpm / 9550 = 1.2 kW.
  • Step 2, gearbox: with a ratio of i = 10, the motor runs at 955 rpm. A gearbox efficiency of 0.96 is assumed; the actual value is given in the gearbox data sheet.
  • Step 3, motor power: Pmotor = 1.2 kW / 0.96 = 1.25 kW. The motor torque is 120 Nm / (10 · 0.96) = 12.5 Nm.
  • Step 4, selecting the motor: the next larger rated power is selected, i.e. at least 1.25 kW, taking into account the duty type and starting conditions.

For linear motions such as hoists, conveyor belts or rack-and-pinion drives, you calculate with P = F · v. Depending on the application, the force is made up of weight force, friction and process forces. With frequent starting, the static load is joined by the acceleration torque, which must overcome the mass inertia of the load and drive. Asynchronous motors can be heavily overloaded for short periods, depending on cooling and the duration of the overload, up to more than twice their rated torque[2]. Short acceleration peaks therefore do not automatically justify a larger motor. The current then results from the motor power, which you can calculate with our article on the current consumption of three-phase motors.

Application factor and duty types

The calculated nominal load describes uniform operation. Real drives experience load shocks, vibrations and starting torques. For gear drives, these additional loads are captured by the application factor KA: it increases the nominal load to take into account all externally introduced additional loads. If measured load spectra are available, KA is calculated as the ratio of equivalent torque to nominal torque. Without such data, DIN 3990 and ISO 6336 provide guide values that depend on the characteristics of the driving and driven machine and lie roughly in the range 1.0 ≤ KA ≤ 2.25[7].

In practice, this means: an electric motor driving a smoothly running pump is at the lower end, while a press or crusher with strong shocks is significantly higher. KA is mainly used in the selection of the gearbox: a gearbox loaded with KA times the nominal torque achieves, by calculation, the same service life as in real operation with changing loads[7]. You select the motor itself according to power requirement and duty type.

The duty type describes how the load is distributed over time. VDE 0530-1 distinguishes, among others[8]:

  • S1: continuous duty with constant load
  • S2: short-time duty with constant load
  • S3: intermittent periodic duty without the influence of starting on heating
  • S4 and S5: intermittent periodic duty with the influence of starting, or starting and braking
  • S6 to S8: continuous operation with intermittent load, with starting and braking, or with load changes

For intermittent duty, the relative duty cycle is specified. If no cycle duration is stated, 10 minutes applies; 20 % duty cycle in S3 therefore means 2 minutes of operation and 8 minutes of rest[8]. Because the motor cools down during the rest periods, it can be loaded more heavily in intermittent duty than in continuous duty. The permissible values for a particular duty cycle are given in the motor data sheet.

IE efficiency classes and partial load

The efficiency classes of mains-fed three-phase motors are governed by DIN EN 60034-30-1 (VDE 0530-30-1). It applies to motors with a rated power of 0.12 kW to 1,000 kW, a rated voltage above 50 V up to 1 kV and 2, 4, 6 or 8 poles[9].

In the EU, the Ecodesign Regulation (EU) 2019/1781 sets minimum requirements. Since 1 July 2021, three-phase motors with 2, 4, 6 or 8 poles from 0.75 kW to 1,000 kW must achieve at least IE3, and smaller ones from 0.12 kW at least IE2. Since 1 July 2023, IE4 has applied to three-phase motors from 75 kW to 200 kW with 2, 4 or 6 poles; exceptions include brake motors and explosion-proof motors. The nominal efficiency and IE class must be permanently marked on or near the nameplate[5].

ClassDesignationMinimum efficiency 11 kW, 4-pole, 50 Hz
IE2High Efficiency89.8 %
IE3Premium Efficiency91.4 %
IE4Super Premium Efficiency93.3 %

The rated efficiency applies at full load. Most electric motors are designed for operation between 50 % and 100 % of the rated load, with the efficiency maximum usually at around 75 %. Below about 50 % load, efficiency drops significantly, and the power factor falls even earlier as the load decreases[6]. A heavily oversized motor therefore loses part of the advantage of its efficiency class.

Typical mistakes in motor selection

Most sizing errors can be traced back to a few patterns:

  • Confusing electrical and mechanical power: if you use the input power Pin as the shaft power, you size the motor and gearbox too small.
  • Forgetting transmission efficiencies: gearboxes, belts and couplings reduce the power that arrives at the load.
  • Applying margins twice: a generous margin on the load plus the next larger motor leads into the partial load range, in which efficiency and power factor drop[6].
  • Ignoring the duty type: a motor designed for S1 can be thermally overloaded in operation with frequent starts.
  • Comparing by kW only: speed, torque requirement, ambient conditions at the installation site and efficiency class belong in every comparison.

You can avoid these mistakes if the motor, gearbox and brake are not designed individually, but as a drive train. As a supplier for the complete drive train, we at ATEK Drive Solutions design the motor, gearbox and brake to fit your load case precisely from a single source. You can find an overview of our IEC standard motors in our product range; we will be happy to advise you on your specific application via our contact page.

Frequently asked questions

How do I calculate the power of an electric motor?

From torque and speed: P = M · n / 9550, with P in kW, M in Nm and n in rpm. The basic formula is P = M · ω = 2π · n · M. The result is the mechanical shaft power.

What does the number 9550 mean in the formula?

It is a conversion factor: 60 · 1000 / 2π ≈ 9549. It converts revolutions per minute into angular velocity and watts into kilowatts. Rounded, 9549 or 9550 is used.

How do I calculate the torque from the motor power?

Rearrange the formula: M = 9550 · P / n. A motor with 5.5 kW at 1,450 rpm delivers around 36 Nm.

Which power is shown on the nameplate?

The rated power, i.e. the delivered mechanical power at the shaft. You get the electrical power consumed by dividing the rated power by the efficiency.

How do I calculate the efficiency and waste heat of an electric motor?

The efficiency is η = Pout / Pin. The waste heat corresponds to the power loss PL = Pin − Pout. An 11 kW motor with 91.4 % efficiency consumes around 12.0 kW and gives off around 1.0 kW as heat.

What is the application factor KA?

A factor by which the nominal load of a gearbox is increased to take into account additional loads such as shocks and load fluctuations. Depending on the driving and driven machine, guide values lie roughly between 1.0 and 2.25.

What does duty type S1 mean?

S1 is continuous duty with constant load. The motor may deliver its rated power continuously. Other duty types such as S2 and S3 apply to short-time and intermittent duty.

Which efficiency class is mandatory for new motors?

According to Regulation (EU) 2019/1781, at least IE3 for three-phase motors from 0.75 to 1,000 kW with 2 to 8 poles, and since July 2023 IE4 for 75 to 200 kW with 2, 4 or 6 poles; exceptions from the IE4 requirement include brake motors.

Sources

  1. Wikipedia (DE): Drehmoment (torque)
  2. Wikipedia (DE): Asynchronmaschine (asynchronous machine)
  3. Wikipedia (DE): Pferdestärke (metric horsepower)
  4. Wikipedia (DE): Wirkungsgrad (efficiency)
  5. Regulation (EU) 2019/1781, Annex I (DE): Ecodesign requirements for electric motors and variable speed drives
  6. U.S. Department of Energy: Determining Electric Motor Load and Efficiency
  7. Gear Technology: Determining value of Ka in regards to DIN 3990 and AGMA standards
  8. Wikipedia (DE): Einschaltdauer (duty cycle)
  9. DKE (DE): DIN EN 60034-30-1 (VDE 0530-30-1) – efficiency classification of mains-fed three-phase motors